Omron S8FS-G01505CD Power supply 15W, 100-240 VAC input, 5VDC, 3A output Din Rail
Availability: Out of stock
₹ 0.0 (+18.0% GST extra)
(Min.Order)
Omron S8FS-G01505CD Power Supply With Cover/DIN Rail Mounting,Covered type,100 to 240 VAC, Power rating 15W, Output: 5VDC, 3A Terminal block (Screw terminal), Harmonic current emissions,Omron Smps,Industrial use for Switch Mode Power Supply, Omron Industrial Smps,
Power rating Item Output voltage |
15 W |
|||||
5 V |
12 V |
15 V |
24 V |
|||
Efficiency * |
100 VAC input |
80% typ. |
84% typ. |
84% typ. |
85% typ. |
|
200 VAC input |
80% typ. |
84% typ. |
84% typ. |
86% typ. |
||
230 VAC input |
80% typ. |
84% typ. |
84% typ. |
86% typ. |
||
Input |
Voltage range * |
Single phase, 85 to 264 VAC, 80 to 370 VDC |
||||
Frequency * |
50/60 Hz (47 to 450 Hz) |
|||||
Current * |
100 VAC input |
0.32 A typ. |
||||
200 VAC input |
0.2 A typ. |
|||||
Power factor |
--- |
|||||
Leakage current * |
100 VAC input |
0.5 mA max. |
||||
200 VAC input |
1 mA max. |
|||||
Inrush current * (for a cold start at 25°C) |
100 VAC input |
14 A typ. |
||||
200 VAC input |
28 A typ. |
|||||
Output |
Rated Output Current |
3 A |
1.3 A |
1 A |
0.65 A |
|
Voltage adjustment range * |
-10% to 15% (with V.ADJ) |
|||||
Ripple & Noise voltage * |
100 to 240 VAC input |
40 mVp-p max. |
40 mVp-p max. |
40 mVp-p max. |
60 mVp-p max. |
|
Input variation influence * |
0.5% max. |
|||||
Load variation influence * |
1.0% max. |
|||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. |
||||
Startup time * |
100 VAC input |
1,000 ms max. |
||||
200 VAC input |
1,000 ms max. |
|||||
Hold time * |
100 VAC input |
15 ms typ. |
14 ms typ. |
15 ms typ. |
15 ms typ. |
|
200 VAC input |
75 ms typ. |
70 ms typ. |
75 ms typ. |
70 ms typ. |
||
Additional functions |
Overload protection |
Yes, automatic reset |
||||
Overvoltage protection * |
Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection |
No |
|||||
Series operation |
Yes (For up to two Power Supplies, external diodes are required.) |
|||||
Parallel operation |
No (However, backup operation is possible, external diodes are required.) |
|||||
Remote sensing |
No |
|||||
Remote control |
No |
|||||
Output indicator |
Yes (LED: Green) |
|||||
Insulation |
Withstand voltage |
3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
Insulation resistance |
100 MÙ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
||||
Storage temperature |
-25 to 75°C (with no condensation or icing) |
|||||
Ambient operating humidity |
90% max. (Storage humidity: 90% max.) |
|||||
Vibration resistance |
10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance |
150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
|||||
Reliability |
MTBF |
135,000 hrs min. |
||||
Life expectancy * |
10 years min. |
|||||
Construction |
Dimensions (W×H×D) |
Refer to Dimensions on page 19. |
||||
Weight |
250 g |
|||||
Cooling fan |
No |
|||||
Degree of protection |
--- |
|||||
Standards |
Harmonic current emissions |
Conforms to EN 61000-3-2 |
||||
EMI * |
Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B |
||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B |
|||||
EMS |
Conforms to EN 61204-3 high severity levels |
|||||
Safety Standards |
UL 508 (Listing, excluding models with connector option) UL 60950-1, UL 62368-1 (Recognition, OVCII [£ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option) EN 50178 (OVCIII [£ 2,000 m], OVCII [> 2,000 m and £ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [£ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) |
|||||
Marine Standards |
No |
|||||
SEMI |
Conforms to F47-0706 (200 VAC input) |